PROCEDURES
100786-0 Rev. D 05/09
1. INSTRUMENT
Sensitivity Ranges: 0-10, 0-50, 0-100, 0-1,000 (1K), and
0-10,000 (10K) ppm
Audible Alarm, continuous: Continuous alarm indicates ame is out.
Audible Alarm, pulsating: Pulsating alarm indicates signal level above
approximately 35 to 45% full meter scale.
Fuel Cylinder Pressure
Indicator: Gauge 0 - 3,000 psig
Fuel Regulator, Internal:
Inlet Pressure, 0 - 1,750 psig; Outlet Pressure,
22 - 42 psig; factory set for 30 cc/min fuel
ow with 1,000 psig in fuel cylinder.
Fuel Cylinder Holder:
Holder located inside instrument to carry fuel
cylinder. See opening at end of instrument.
Weight of Instrument: 7 lbs. (3.2 kg), Operating
2. PROBE, Sample
Adjustable Length: 25 to 41 inches (63 to 104 cm)
Weight: 12 oz. (.340 kg)
3. BATTERY CHARGER
Automatic Reduction: 16 hours to full charge
Power: 110 VAC, 60 Hz
Output: 14.5 VDC at 60ma
4. FILTRATION
Replaceable Filters: Part No. 0110163, Pkg/100 or
Part No. 0110683, Pkg/500